Winters, LMH3600, LMH 0/3,600 PSI 1/4″ NPT Hydraulic Pressure Transmitter
Features:
- Developed for use in heavy duty industrial applications
- Compact stainless steel construction with welded stainless steel sensor
- Available ranges up to 8,7000 PSI
- Wide range of mechanical and electrical connections
- ±0.5% accuracy
- NEMA 4x / IP65 and IP67
- CE and RoHS compliant
- Customizable
- 1 year warranty
Applications:
- Suitable for heavy duty process and automation control including mobile hydraulics and presses
| Range |
0/3,600 PSI |
| Over-pressure |
10,150 PSI |
| Burst Pressure |
20,305 PSI |
| Output Signal |
Standard 2-wire: 4-20 mA / Vs = 8-32 Vdc Optional 3-wire: 0-10 V / Vs = 14-30 Vdc Optional 3-wire ratiometric: Vsig = 0.5-4.5 Vs / Vs = 5 ± 0.5 Vdc |
| Accuracy |
±0.5% FSO |
| Permissible Load |
2-wire: Rmax = [(Vs – Vs min) / 0.02] Ohm 3-wire: Rmin = 10 kOhm |
| Influence Effects |
Supply: 0.05% FSO / 10 VLoad: 0.05% FSO / kOhm |
| Response Time |
2-wire: ?10 ms 3-wire: ?3 ms |
| Measuring Rate |
1 kHz |
| Thermal Error |
<±0.3% FSO / 10Km, Compensated range 32°F to 158°F (0°C to 70°C) |
| Permissible Temperatures |
Medium: -40°F to 257°F (-40°C to 125°C) Electronics environment: -40°F to 185°F (-40°C to 85°C) Storage: -40°F to 185°F (-40°C to 85°C) |
| Short-circuit Protection |
Permanent 3-wire ratiometric: None |
| Reverse Polarity Protection |
No damage. No function. |
| Electromagnetic Protection |
Emission and immunity according to EN 61326 |
| Stability |
Vibration: 20 g, 25 Hz to 2 kHz according to DIN EN 60068-2-6 Shock: 500 g / 1 ms according to DIN EN 60068-2-27 |
| Pressure Port |
316Ti SS |
| Pressure Port Connection |
1/4″ NPT (others available upon request) |
| Housing |
304 SS |
| Diaphragm |
17-4PH SS, welded |
| Weight |
120 g |
| Current Consumption |
2-wire: 25 mA max 3-wire voltage: 5 mA (short-circuit current 20 mA) 3-wire ratiometric: 3 mA |
| Long-term Stability |
<±0.3% FSO/yr at reference conditions |
| Operation Life |
>100 x 106cycles |
| CE Conformity |
EMC directive: 2004/108/EC Pressure equipment directive: 97/23/EC (module A). Valid for devices with max permissible overpressure> 3,000 PSI |
</table